Control (power) cable
oil-resistant multi-use like temperature measurement for hot-runner control systems
Article-No. | Zones | Identifier | Outer Sheath | M. Ø ca. mm |
---|---|---|---|---|
2Z9305S | 2 | 5 G 1,5 qmm | PVC | 6,7 mm |
2Z9405S | 2 | 5 G 2,5 qmm | PVC | 8,1 mm |
3Z9307S | 3 | 7 G 1,5 qmm | PVC | 8,9 mm |
3Z9407S | 3 | 7 G 2,5 qmm | PVC | 11,1 mm |
4Z9309S | 4 | 9 G 1,5 qmm | PVC | 11,4 mm |
4Z9310S | 4 | 10 G 1,5 qmm | PVC | 11,6 mm |
6Z9314S | 6 | 14 G 1,5 qmm | PVC | 12,7 mm |
6Z9414S | 6 | 14 G 2,5 qmm | PVC | 15,8 mm |
8Z9318S | 8 | 18 G 1,5 qmm | PVC | 14,4 mm |
8Z9418S | 8 | 18 G 2,5 qmm | PVC | 17,8 mm |
12Z9325S | 12 | 25 G 1,5 qmm | PVC | 16,9 mm |
12Z9425S | 12 | 25 G 2,5 qmm | PVC | 20,8 mm |
16Z9134S | 16 | 34 G 0,75 qmm | PVC | 15,9 mm |
16Z9334S | 16 | 34 G 1,5 qmm | PVC | 19,4 mm |
16Z9434S | 16 | 34 G 2,5 qmm | PVC | 24,4 mm |
24Z9150S | 24 | 50 G 0,75 qmm | PVC | 19,9 mm |
24Z9350S | 24 | 50 G 1,5 qmm | PVC | 23,5 mm |
24Z9450S | 24 | 50 G 2,5 qmm | PVC | 29,4 mm |
32Z9065S | 32 | 65 G 0,5 qmm | PVC | 19,6 mm |
32Z9165S | 32 | 65 G 0,75 qmm | PVC | 21,8 mm |
36Z9080S | 36 | 80 G 0,5 qmm | PVC | 21,1 mm |
36Z9180S | 36 | 80 G 0,75 qmm | PVC | 23,6 mm |
No minimum quantities
Earth conductor: G = with earth conductor
Application range
Fixed laying as well as infrequent flexible use without tensile load in free, not repeatedly occurring movement. Dry or damp rooms with average mechanical strain.
Applicable for connection between hot runner and control device. Mantle material PVC, grey (RAL 7001)
Temperature range: infrequently moved: -15°C up to +70°C
In power track trains: -5°C up to +70°C
Fixed laying: -40°C up to +80°C
Cables are suitable for flexible use and fixed laying in dry and damp rooms with average mechanical strain. May not be used outdoor without UV-protection and only in consideration of the min./max. temperature range.
Norm-references / approvals VDE Reg.-Nr. 7030 for following dimensions:
up to 2,5 mm²: 2 - 65 leads, from 4 mm²: 2 - 7 leads, from 25 mm²: 2 - 5 leads
Product properties:
Flame-retardant compliant to IEC 60332-1-2
Good chemical durability, see catalogue annex T1
oil resistant compliant to DIN EN 50290-2-22 (TM54)
The fotos are not to scale and not detailed pictures of the specific products
Technical Data
Lead-Ident-Code: Black with white numbers compliant to VDE 0293-1
Classification: ETIM 5.0 Class-ID: EC000104
ETIM 5.0 Class-Description: control line
Isolation spezific
contact resistance:
> 20 GOhm x cm
Wire dress: finde-wired compliant to DIN EN 60228 (VDE 0295), Class 5 / IEC
60228 class 5
Torsion application in WKA: TW-0 & TW-1, see annex T0
Minimum bending range: infrequently moved: 10 x outer diameter
In power track train: 15 x outer diameter
Fixed laying: 4 x outer diameter
Nominal voltage: U₀/U: 300/500 V
Proof voltage: 4000 V